2012 Ford Pickup

  • 2012 Ford Pickup

    Ford Pickup
    Mileage
    161,012
    Service Date
    9/5/2024
    Services Performed
    • Blower motor is inoperative at all speeds, pigtail and speed control module have a melted terminal. Compressor clutch does not engage. Can hear one of the hvac actuators clicking. B1086-air distribution damper motor B10B9-blower control circuit short to ground or open B11E5-left hvac damper position sensor circuit short to battery or open Jumpered blower motor ground, drivers side vent temps at 49 degrees at idle, passenger side is stuck on full heat. Drivers side blend motor moves from full hot to full cold, but sticks at full hot and clicks for about 15 seconds before moving to cold. Recommend replace both blend door actuators, blower resistor and pigtail, then service a/c system and recheck operation.
    • Removed instrument cluster and dash assembly. Removed heater/ac box. Replaced both left and right temperature control actuators. During repair found control rod from recirculation actuator broken. Repaired rod since no replacement part is available. Replaced blower motor and resistor. Charged ac system to specification and added oil and dye to system. Received 44 degree air temp on ac and 160 on heat.
     